125
CHAPTER 8 FUNCTIONS
8
8.14 Difference Conversion Function
(b) Operation when Initial data setting request flag (RY9) is switched
During difference conversion, turning on and off Initial data setting request flag (RY9) results in the
difference conversion continuing without updating the difference conversion reference value. At this time,
even if the digital clipping function, scaling function, and shift function are set valid, the difference
conversion reference value is not updated. To update the difference conversion reference value, change
CH Difference conversion trigger (RY14 to RY17, RY24 to RY27) as follows: Trigger request (ON)No
request (OFF)Trigger request (ON).
Before CH A/D conversion completed flag (RX10 to RX13, RX20 to RX23) turns on from off by turning
on Initial data setting request flag (RY9) from off, changing CH Difference conversion trigger (RY14 to
RY17, RY24 to RY27) from No request (OFF) to Trigger request (ON) results in operation with the
difference conversion reference value taking on the digital operation value at the time when CH A/D
conversion completed flag (RX10 to RX13, RX20 to RX23) turns on from off.
Digital output value
CH Difference conversion reference
value
(RWr6 to RWr9, RWr16 to RWr19)
CH Difference conversion state flag
(RX14 to RX17, RX24 to RX27)
CH Digital operation value
(RWr2 to RWr5, RWr12 to RWr15)
CH Difference conversion trigger
(RY14 to RY17, RY24 to RY27)
Initial data setting completion
flag (RX9)
Initial data setting request
flag (RY9)
Updated
Not updated
9950 1300010001 10100 10010 10510 12000 12100 13250 13310
10000 1300010000 10000 10000 10000 10000 10000 10000 13000
-50 01 100 10 510 2000 12100 13250 310
ON
ON
ON ON
ON ON
OFFOFF
OFF
OFF
OFF
OFF

Table of Contents

Related product manuals