174
017H Moderate error
External signal
assignment setting
error
The addresses set in the external signal
assignment function are different from those
assigned to the extension I/O module.
indicates a type of the following errors:
0: Trigger conversion function
1: Input signal error detection function
2: Alert output function
3: Error output
4: Warning output
Adjust the external signal assignment function to
fall within the addresses assigned to the extension
I/O module.
0180H Moderate error
Same address for
the external signal
assignment function
The same address has been set in multiple
extension output modules for the external
signal assignment function.
Set a unique address.
020H
*1
Moderate error
Averaging time
setting out-of-range
The averaging time value set in CH Time
average/Count average/Moving average
(address: 0105H to 0108H) is outside the
range of 2 to 5000ms.
indicates the number of the channel where
an error has occurred.
Set the averaging time to a value in the range of 2
to 5000ms.
The time average value set in CH Time
average/Count average/Moving average
(address: 0105H to 0108H) is less than "4 ×
Sampling period" (ms).
indicates the number of the channel where
an error has occurred.
Adjust the time average value to be equal to or
greater than "4 × Sampling period" (ms).
030H
*1
Moderate error
Count average
setting out-of-range
The averaging count value set in CH Time
average/Count average/Moving average
(address: 0105H to 0108H) is outside the
range of 4 to 65000.
indicates the number of the channel where
an error has occurred.
Set the averaging count to a value in the range of
4 to 65000.
031H
*1
Moderate error
Moving average
setting out-of-range
The moving average count value set in CH
Time average/Count average/Moving average
(address: 0105H to 0108H) is outside the
range of 2 to 128.
indicates the number of the channel where
an error has occurred.
Set the moving average count to a value in the
range of 2 to 128.
0360H
*1
Moderate error
Conversion speed
setting out-of-range
The value set in Conversion speed setting
(address: 0001H) is other than 0 and 2.
Set one of the following values in Conversion
speed setting (address: 0001H).
• 400μs/channel (0H)
• 1ms/channel (1H)
• 100μs/channel (2H)
040H
*1
Moderate error
Offset/gain setting
value inverted
The user range setting value has been set to a
value where the offset value is equal to or
greater than the gain value.
indicates the number of the channel where
an error has occurred.
Correct the setting so that the offset value is
smaller than the gain value.
06H
*1
Moderate error
Process alarm
setting error
The settings in CH1 Process alarm lower lower
limit value (address: 010FH) to CH4 Process
alarm upper upper limit value (address:
011EH) are invalid.
indicates the number of the channel that has
been incorrectly set.
indicates that the set values are in one of
the following conditions:
2: Process alarm lower lower limit value >
Process alarm lower upper limit value
3: Process alarm lower upper limit value >
Process alarm upper lower limit value
4: Process alarm upper lower limit value >
Process alarm upper upper limit value
Correct the settings in CH1 Process alarm lower
lower limit value (address: 010FH) to CH4
Process alarm upper upper limit value (address:
011EH).
0730H Moderate error
Mode switch setting
error
A value out of the range is set in mode switch
(address: 0000H).
Reset the mode switch (address: 0000H) to either
of the followings.
• Normal Mode (0H)
• Trigger conversion mode (1H)
• Automatical judgment mode (9H)
Error code
(hexadecimal)
Classification Error name Description and cause Action