196
(10)Maximum value/minimum value reset completed flag
This signal turns on when the maximum value stored in CH Maximum value (address: 0601H, 0603H, 0605H,
0607H, 0701H, 0703H, 0705H, 0707H) and the minimum value stored in CH Minimum value (address: 0602H,
0604H, 0606H, 0608H, 0702H, 0704H, 0706H, 0708H) are reset by turning on and off Maximum value/minimum
value reset request (RY1D).
(a) Device number
The device numbers of this input signal are as follows:
(11)External power supply monitor state flag
This signal turns on when the external power supply monitoring function is being activated by External power
supply monitor request flag (RY1F).
For the external power supply monitoring function, refer to the following:
External power supply monitoring function ( Page 145, Section 8.18.1 (1))
(a) Device number
The device number of this input signal is as follows:
Signal name Main A/D converter module Extension A/D converter module
Maximum value/minimum value reset
completed flag
RX1D RX2D
Signal name Main A/D converter module Extension A/D converter module
External power supply monitor state flag RX1F
Controlled by the A/D converter module
CH Maximum value
(address: 0601H, 0603H, 0605H, 0607H,
1601H, 1603H, 1605H, 1607H)
CH Minimum value
(address: 0602H, 0604H, 0606H, 0608H,
1602H, 1604H, 1606H, 1608H)
Maximum value/minimum value reset
request (RY1D, RY2D)
Maximum value/minimum value reset
completed flag (RX1D, RX2D)
Controlled by the program
Maximum value and
minimum value before reset
Maximum value and
minimum value after reset
ON
ON
OFF
OFF
OFF
OFF
External power supply monitor
function
External power supply monitor
request flag (RY1F)
Changed by user
OFF
OFF
ON
ON
OFF
OFF
Controlled by the A/D converter module
Changed by user
External power supply monitor
status flag (RX1F)
Disabled Enabled Disabled