210
(7) Warning flag assignment
Assign Warning flag (RX7) to Remote output (RY) of the extension output module using the external signal
assignment function. When a minor error occurs, assigned Remote output (RY) is turned on.
(a) Setting range
With the head of Remote output (RY) of the main A/D converter module as a starting point (0000H), set the
device number for Remote output (RY) of the connected extension output module.
When Warning flag (RX7) is assigned to Remote output (RY) numbered 6H as counted from the head
(0H) of the extension output module
Remote output (RY) numbered 6H as counted from the head of the extension output module corresponds
to Remote output (RY) numbered 26H as counted from the head of the main A/D converter module.
Thus, set 26H for Warning flag assignment (address: 0006H).
(b) Enabling the setting
Turn on and off Initial data setting request flag (RY9) to enable the setting.
(c) Default value
The default value is No assignment (FFFFH).
(d) Remote buffer memory address
The remote buffer memory address of this area is as follows:
Setting a value out of the range results in the error code (0174H) being stored in Latest error code (RWr0), Error flag (RXA)
turning on, and the ERR. LED lighting up, with the previously set operation.
Remote buffer memory name Main A/D converter module Extension A/D converter module
Warning flag assignment 0006H
0H to to to1FH 20H 26H 2FH
to to0H 6H FH
Main A/D converter module Extension output module