6 - 98
: Self-diagnostics is performed, : Self-diagnostics is not performed
(To the next page)
Table6.27 Self-diagnostics list (continued)
Diagnostics
Error
message
Diagnostic timing
CPU
module
status
LED status Basic
model
QCPU
High
Performance
model QCPU
Process
CPU
Redundant
CPU
RUN ERR.
Parame-
ter error
SFC
parameter
error
SFC
PARA.ERR
OR
Switching from STOP to
RUN
Writing to programmable
controller
Stop Off Flashing
Intelligent
function
module
parameter
error
SP.PARA.
ERROR
Power-on/reset Stop Off Flashing
Password error
REMOTE
PASS.ERR
Power-on/reset
Switching from STOP to
RUN
Stop Off Flashing
Instruction code check
INSTRUCT.
CODE ERR
Power-on/reset
Switching from STOP to
RUN
Execution of an
instruction
Stop Off Flashing
No END instruction
MISSING
END INS.
Power-on/reset
Switching from STOP to
RUN
Stop Off Flashing
Pointer setting error
CAN'T
SET(P)
Power-on/reset
Switching from STOP to
RUN
Stop Off Flashing
CAN'T
SET(I)
Power-on/reset
Switching from STOP to
RUN
Stop Off Flashing
Program
error
Operation
error*1 *4
OPERA-
TION
ERROR
Execution of an
instruction
Stop/
Continue
Off/
On
Flashing/
On
FOR to NEXT
instructions
structure
error
FOR NEXT
ERROR
Execution of an
instruction
Stop Off Flashing
CALL to RET
instructions
structure
error
CAN'T
EXECUTE
(P)
Execution of an
instruction
Stop Off Flashing
Interrupt
program error
CAN'T
EXECUTE
(I)
Execution of an
instruction
Stop Off Flashing
Instruction
execution
disabled
INST.
FORMAT
ERR.
Execution of an
instruction
S
top Off Flashing
SFC program
structure
error
SFCP.COD
E ERROR
Switching from STOP to
RUN
Stop Off Flashing
SFC block
configuration
error
CAN'T
SET(BL)
Switching from STOP to
RUN
Stop Off Flashing

Table of Contents