EasyManuals Logo

Mitsubishi MELSEC-Q/L User Manual

Mitsubishi MELSEC-Q/L
850 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #749 background imageLoading...
Page #749 background image
747
3
2
3
A
5
6
7
8
Appendix 1OPERATION PROCESSING TIME
Appendix 1.4Operation Processing Time of Universal Model QCPU
Category Instruction Condition (Device)
Processing Time (µs)
Q00UJCPU Q00UCPU Q01UCPU Q02UCPU
Min. Max. Min. Max. Min. Max. Min. Max.
Basic
instruction
LD<>
In conductive status
0.360 0.240 0.180 0.120
In non-conductive status
AND<>
When not executed
0.360 0.240 0.180 0.120
When executed
In conductive status
In non-conductive status
OR<>
When not executed
0.360 0.240 0.180 0.120
When executed
In conductive status
In non-conductive status
LD>
In conductive status
0.360 0.240 0.180 0.120
In non-conductive status
AND>
When not executed
0.360 0.240 0.180 0.120
When executed
In conductive status
In non-conductive status
OR>
When not executed
0.360 0.240 0.180 0.120
When executed
In conductive status
In non-conductive status
LD<=
In conductive status
0.360 0.240 0.180 0.120
In non-conductive status
AND<=
When not executed
0.360 0.240 0.180 0.120
When executed
In conductive status
In non-conductive status
OR<=
When not executed
0.360 0.240 0.180 0.120
When executed
In conductive status
In non-conductive status
LD<
In conductive status
0.360 0.240 0.180 0.120
In non-conductive status
AND<
When not executed
0.360 0.240 0.180 0.120
When executed
In conductive status
In non-conductive status
OR<
When not executed
0.360 0.240 0.180 0.120
When executed
In conductive status
In non-conductive status
LD>=
In conductive status
0.360 0.240 0.180 0.120
In non-conductive status
AND>=
When not executed
0.360 0.240 0.180 0.120
When executed
In conductive status
In non-conductive status
OR>=
When not executed
0.360 0.240 0.180 0.120
When executed
In conductive status
In non-conductive status
LDD=
In conductive status
0.360 0.240 0.180 0.120
In non-conductive status
ANDD=
When not executed
0.360 0.240 0.180 0.120
When executed
In conductive status
In non-conductive status
ORD=
When not executed
0.360 0.240 0.180 0.120
When executed
In conductive status
In non-conductive status
LDD<>
In conductive status
0.360 0.240 0.180 0.120
In non-conductive status
ANDD<>
When not executed
0.360 0.240 0.180 0.120
When executed
In conductive status
In non-conductive status

Table of Contents