Page #750 background image
748
Category Instruction Condition (Device)
Processing Time (µs)
Q00UJCPU Q00UCPU Q01UCPU Q02UCPU
Min. Max. Min. Max. Min. Max. Min. Max.
Basic
instruction
ORD<>
When not executed
0.360 0.240 0.180 0.120
When
executed
In conductive status
In non-conductive status
LDD>
In conductive status
0.360 0.240 0.180 0.120
In non-conductive status
ANDD>
When not executed
0.360 0.240 0.180 0.120
When
executed
In conductive status
In non-conductive status
ORD>
When not executed
0.360 0.240 0.180 0.120
When
executed
In conductive status
In non-conductive status
LDD<=
In conductive status
0.360 0.240 0.180 0.120
In non-conductive status
ANDD<=
When not executed
0.360 0.240 0.180 0.120
When
executed
In conductive status
In non-conductive status
ORD<=
When not executed
0.360 0.240 0.180 0.120
When
executed
In conductive status
In non-conductive status
LDD<
In conductive status
0.360 0.240 0.180 0.120
In non-conductive status
ANDD<
When not executed
0.360 0.240 0.180 0.120
When
executed
In conductive status
In non-conductive status
ORD<
When not executed
0.360 0.240 0.180 0.120
When
executed
In conductive status
In non-conductive status
LDD>=
In conductive status
0.360 0.240 0.180 0.120
In non-conductive status
ANDD>=
When not executed
0.360 0.240 0.180 0.120
When
executed
In conductive status
In non-conductive status
ORD>=
When not executed
0.360 0.240 0.180 0.120
When
executed
In conductive status
In non-conductive status
+
When executed
0.360 0.240 0.180 0.120
+
When executed
0.480 0.320 0.240 0.160
-
When executed
0.360 0.240 0.180 0.120
-
When executed
0.480 0.320 0.240 0.160
D +
When executed
0.360 0.240 0.180 0.120
D +
When executed
0.480 0.320 0.240 0.160
D -
When executed
0.360 0.240 0.180 0.120
D -
When executed
0.480 0.320 0.240 0.160
*
When executed
0.420 0.300 0.240 0.180
/
When executed
0.520 0.400 0.340 0.280
D *
When executed
0.500 0.380 0.320 0.260
D/
When executed
0.640 0.520 0.460 0.400
B +
When executed
3.100 12.300 3.100 12.300 3.100 12.300 3.300 8.300
B +
When executed
5.900 13.500 5.900 13.500 5.900 13.500 4.600 6.200
B -
When executed
3.150 12.300 3.150 12.300 3.150 12.300 3.300 9.000
B -
When executed
5.950 13.600 5.950 13.600 5.950 13.600 4.600 8.200
S
D
S1
S2
D
S
D
S1
S2
D
S
D
S1
S2
D
S
D
S1
S2
D
S1
S2
D
S1
S2
D
S1
S2
D
S1
S2
D
S
D
S1
S2
D
S
D
S1
S2
D

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi MELSEC-Q/L and is the answer not in the manual?

Mitsubishi MELSEC-Q/L Specifications

General IconGeneral
BrandMitsubishi
ModelMELSEC-Q/L
CategoryController
LanguageEnglish

Related product manuals