Section 3: Installation
mCore is approved for Class I Div. 2 Group A, B, C, and D. In order to maintain this
rating, the unit must be installed in a separate tool secured enclosure and comply with
the one of the following NEC wiring methods:
1. Extra-hard usage cord – Section 501.140 of the NEC and Rule J18-160 of the CE
Code Part I.
2. Instrumentation tray cable (Type ITC or CIC) – Section 501.10(B) and
501.105(B)(6) of the NEC and Rule J18-152 of the CE Code Part I.
3. Power-limited tray cable (Type PLTC) – Article 725 of the NEC.
4. Tray cable (Type TC) installed per Article 336 of the NEC and Rule 12-2202 of the
CE Code Part I.