Motion 3000ES Escalator Control
46 Manual # 42-02-E001
Table 14. KEB F5 Parameters for Escalator Applications
WARNING: Do not change drive parameters while escalator is running. Incorrect drive parameters can
cause erratic operation.
WARNING: Parameters with an asterisk (*) must be set correctly for your specific motor/machine/job.
Param Description Unit Default MCE
CP.00 Password - - -
CP.01 Motor Rated Power (KW = HP x 0.75) KW 7.5
CP.02 Motor Rated Current A
CP.03 Motor Electronic Overload Current A
CP.04 Motor Rated Voltage V 460 *
CP.05 Motor Rated Frequency Hz 60 *
CP.06 Motor Rated Power Factor - 0.85 0.85
CP.07 Motor Rated Frequency Hz 60 *
CP.08 Low Speed Torque Boost % 5.0 5.0
CP.09 Voltage Regulation (Set equal to motor voltage) V 460 *
CP.10 Energy Saving Factor % 50 ** 50
CP.11 Low Speed (recommend 50% of High Speed CP.13) Hz 10.0000 **
CP.12 Inspection Speed Hz 35.0000 ** 10.0000
CP.13 High Speed Hz 60.0000 **
CP.14 Line Frequency (Set 1Hz lower than line frequency) Hz 59.0000
CP.15 Acc Time sec 5.00 **5.00
CP.16 Dec Time sec 5.00 **5.00
CP.17 Drive Contactor Turn OFF Timer mSec 100.00 100.00
CP.18 Drive Contactor Turn ON Timer mSec 1000.00 1000.00
CP.19 Line Contactor Turn ON Timer mSec 1000.00 1000.00
CP.20 Energy Saving Trigger Level. (Set 2A higher than idle current
running full speed up. Monitor CP.21 to see actual current.)
A - CP.21 + 2A
CP.21 Phase Current A - Read Only
CP.22 Peak Phase Current (Press Down key to reset) A - Read Only
CP.23 Actual Frequency Display Hz - Read Only
CP.24 Output Voltage V - Read Only
CP.25 Actual DC Voltage V - Read Only
CP.26 Peak DC Voltage (Press Down key to reset) V - Read Only
CP.27 Input terminal state. (Display active inputs. See Table 17 for
decoding values)
-0: no
input
Read Only
CP.28 Inverter State - - Read Only
CP.29 Function select (Selects which functions are active. See Table
16 for available setting.)
-4
CP.30 Escalator status mode (Display current mode of operation.
See Table 15 to decode number.)
--Read Only