12 Technical data
103BA6820378-03 EN
12.1 Technical data
Operating conditions
Location of use Indoors and outdoors
Contamination level 4
Relative humidity (operation and
storage)
Inside the connection box: 5 to 95% (non-con-
densing)
Ambient temperature DB100/200/200D: 0...+70°C / -50...+70°C HT
version*;
DB200G: 0...+70°C / -20...+70°C HT version*;
It's will*) HT version for applications in cold re-
gions, i.e. ambient temperature is continuously
below 0°C over a time period of 20days.
Storage temperature -50 °C...+70°C
Degree of protection (terminal box) IP66/IP67 in accordance with IEC60529
Overvoltage category III
Protection class I
Installation altitude 2,000m above sea level
Design types
Materials All external parts are resistant to weathering
and UV radiation; version with resistance to
saltwater (offshore) optional
Color Flanges and metal parts: anodized (aluminum)
Connection box:
Powder-coated (C4H or CX in accordance with
DIN EN ISO 12944-9 as an option) or
RAL7033 (cement gray) or
RAL7038 (agate gray)
Weight (without flange) DB100: approx. 8.6kg
DB200: approx. 12.6kg
DB200D: approx. 23.6kg
DB200G: approx. 31.6kg
Dimensions See section Dimensional drawings