9 Error messages and troubleshooting
83BA6820378-03 EN
Prior to opening the terminal box or when checking the cables and sensors,
always observe the following safety information:
WARNING
Electric shock
Risk of fatal injury due to electrical voltage.
De-energize the device and system peripherals and take measures to
ensure that they cannot be switched back on.
If you would like to acknowledge an error that is no longer
present, press the test button on the side of the terminal box. If
several errors were present, these are to be acknowledged in-
dividually one after the other. The LED signaling is then reset
and the signaling relay for device malfunctions (failsafe) picks
up again after all errors have been acknowledged.
If an error occurs that you cannot remedy yourself, please contact:
Maschinenfabrik Reinhausen GmbH
MR Service & Complaint
Falkensteinstrasse 8
93059 Regensburg
Germany
E-mail: service@reinhausen.com
E-mail: complaint@reinhausen.com
Using the self-monitoring function, the device identifies internal errors and
signals them by illuminating and flashing LEDs in different ways . In
addition, an error is signaled via the device error relay (failsafe) [Section
6.7, Page 60].
The device error relay is energized in normal operation and
drops out after a delay (> 7 seconds) after switching off the
supply voltage so as to avoid generating an error message
during short interruptions of the supply voltage.