6 Electrical connection
55BA6820378-03 EN
To prepare the cable correctly, proceed as follows:
1. Open the terminal box of the dehydrating breather. To do so, unscrew the
4 captive screws on the housing cover. The cover is held on the left-hand
side via spring hinges and can be swung open to the left. The cover of the
terminal box is grounded with a grounding cable
Figure34: Uninstalling the cover of the terminal box
2. Remove the supply voltage cable jacket and cut the cable such that the
length of the PE wire is 50mm longer than the wires for L and N. Strip
7mm (1/4″) of the insulation from the wires.
Figure35: Preparing the cable