8.2 Specifications
8.2.1 System Specifications
Typical Response Time: 10 seconds, see 9 Certifications for FM Approval response times
Field of View*: ±30° @ 210 ft (64 m), ±45° @ 110 ft (34 m), 90° total field of view
Sensitivity:
310 ft (95 m), 140 ft (43 m), and 70 ft (21 m) for high, medium, and low sensitivities,
respectively. Maximum distance for a 1 square foot (0.093 m
2
) n-heptane fire to be reliably
detected. For settings see 5.7 Switch Selectable Options.
* Maximum specified FOV is the angle at which FL5000 can detect the flame at 50% of the maximum specified range. To
comply with the directional dependence requirements for EN 54-10:2002, an angle of ± 30° from 0°(0° = Orientation of
detector in same axes as flame source) should not be exceeded, based on lab testing at a distance of approximately 5.9 ft
(1.8 m).
NOTE: Response Times and Field of View data were obtained from tests with a 1 square foot heptane fire. These are
typical values and different results may occur depending on the variation of each fire.
8.2.2 Mechanical Specifications
Enclosure Material: 316 Stainless Steel
Color: Red
Finish: Polyester TGICPowder Coating
Vibration: Tested to the vibration requirements of FM 3260, EN 54-10 and DNV-CG-0339 (Class A)
8.2.3 Dimensions
Height: 4.15" (105 mm)
Diameter:
5.44” (138 mm) Base
3.50" (89 mm) Optical Housing
Weight: 7.6 lbs (3.447 kg)
Weight (w/ mount bracket): 9.125lbs (4.139 kg)
8.2.4 Environmental Specifications
Operating temperature range:
-40°F to 176°F (-40°C to 80°C) - FM3260 & ULC-ORD-C386
-67°F to 176°F (-55°C to 80°C) - EN54-10 & DNV-CG-0339
Storage temperature range:
-40°F to 176°F (-40°C to 80°C) - FM3260 & ULC-ORD-C386
-67°F to 176°F (-55°C to 80°C) - EN54-10 & DNV-CG-0339
Humidity range: 0% to 95% RH, non-condensing