34 FL5000 Multi-Spectrum Flame Detector US
5 Installation
5.7 Switch Selectable Options
All settings on the FL5000 are selected via a dipswitch on the Power/Relay board or via Modbus (overrides switch
settings).
To set these options:
1. Remove the detector head from the Base Assembly and locate the dipswitch per the Dipswitch Location figure in
5.7.1 Time Delay Settings
2. On the dipswitch, ON/CLOSED means the switch is pushed in on the side labeled ON or CLOSED (opposite the
OPEN side).
3. OFF/OPEN means the switch is pushed in on the side with the number corresponding to the switch position or the
side labeled OPEN ā refer to 5.7.1 Time Delay Settings for dipswitch assignments.
The settings for the INSTANT ALARM and SUSTAINED ALARM outputs are covered in 5.6 Terminal Connections.
Figure 19 Dipswitch Location