6. Tap the Name textbox to rename the relay.
7. Select the Horn checkbox, as needed.
8. Tap OK.
9. Repeat steps 1-5 as needed.
10.Tap Next to proceed to the Voting Zones configuration.
NOTE: You cannot go back in the process once you tap
Next.
4.6 Voting Zones
The SENTRY io logic programming supports “OR” gate and “AND” gate logic functions in the SmartStart setup wizard. Any
OR gates may be selected in zoning logic section, or “2 of N” or “3 of N” are also selectable to achieve limited “AND” gate
functions.
Voting zones are only needed if you want to achieve “OR,” “2 of N,” or “3 of N” logic voting . " AND" logic can be achieved in
the cause and effect logic configured after voting zones.
1. Select whether or not you want to set voting zones.
If Yes, proceed to step 2.
If No, you automatically proceed to the Cause and Effect
configuration. See 4.7 Cause and Effect for more
information.
2. Tap the Voting Zone textbox, select a zone by swiping or
using and to locate the desired zone number, and
tap Ok.
3. If needed, tap the name of the voting zone to rename it.
4. Tap the Logic textbox, swipe or use and to select
"and," "or," "2 of n," or "3 of n," and tap Ok.
5. Tap the Channel textbox, select a channel by swiping or
using and to locate the desired channel, and tap Ok.
Once a channel is selected, the digital input, relay, and alarm
selections are available.