FPΣ
8.1 Computer Link
8-9
- Commands and responses used with the FPΣ have a dedicated
header (start code) added to the “MEWTOCOL-COM” communica-
tion protocol of the FP series PLC.
- The contents of the specified header vary depending on the commu-
nication conditions.
- With the FPΣ, in addition to ordinary MEWTOCOL-COM, an expan-
sion header is also supported that enables single frames of up to
2,048 characters to be sent.
Tip
- The number of characters that can be sent is restricted by the type
of header and the command.
No. of characters that can be sent in 1 frame
Max. 118 characters
Max. 2048 characters
Type of header
%
<