5.1 Installation
This section explains installation environment and installation method of FPΣ.
5.1.1 Installation Environment and Space
Avoid installing the unit in the following locations:
- Ambient temperatures outside the range of 0°Cto
55°C/32°F to 131°F
- Ambient humidity outside the range of 30% to 85% RH
- Sudden temperature changes causing condensation
- Inflammable or corrosive gases
- Excessive airborne dust, metal particles or salts
- Benzine, paint thinner, alcohol or other organic solvents or
strong alkaline solutions such as ammonia or caustic soda
- Excessive vibration or shock
- Direct sunlight
- Water or oil in any form including spray or mist
Measures regarding noise:
- Influence from power transmission lines, high voltage
equipment, power cables, power equipment, radio
transmitters, or any other equipment that would generate
high switching surges
- If noise occurs in the power supply line even after the
above countermeasures are taken, it is recommended to
supply power through an insulation transformer, noise
filter, or like.