EasyManua.ls Logo

Neptronic SKE4-E Series - Plumbing Connections; General Plumbing Connection Guidelines

Neptronic SKE4-E Series
76 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SKE4-E Steam Humidifier
Installation Instructions and User Manual
www.neptronic.com
Page | - 29 -
Plumbing Connections
Plumbing Installation must conform to Local and National Codes.
Any installation work must be carried out by suitably qualified personnel.
The SKE4 humidifier can operate with tap, reverse osmosis and deionised water.
x For normal operation, pre-treatment of water is not necessary.
x For ultrapure deionised or reverse osmosis water (2-10 µS/cm), the ultrapure humidifier
option must be used.
x The chde ccea  he hdfe eaa chabe  ea be 10
(20ppm for ultrapure water).
x As the humidifier is equipped with the Neptronic Anti-Foaming Energy Conservation (AFEC)
system, which drains the humidifier in the presence of foam to ensure clean and safe
operation, the use of softened water is not required.
If a third party requires a water softener for any operational or equivalency purposes, ensure
that the water dilution feature is enabled. To enable this function, configure the value of the
BlowdownRate setting located in the Installation menu (see page 52 for details).
Illustration 29 - Plumbing Connections for Models SKE4-E05 to E80 (Bottom View)
Table 9 - Dimensions for Plumbing Connections (SKE4-E05 to E80)
Model
Dimensions (mm)
A
B
C
D
E
F
SKE4-E05
270
178
38
51
73
83
SKE4-E10
SKE4-E20
SKE4-E30
SKE4-E40
SKE4-E50
SKE4-E60
SKE4-E80
304
178
38
51
73
83

Table of Contents