EasyManua.ls Logo

Neptronic SKE4-E Series - General Menu Settings; Status Parameters; Control Parameters; Physical IO Status

Neptronic SKE4-E Series
76 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SKE4-E Steam Humidifier
Installation Instructions and User Manual
www.neptronic.com
Page | - 47 -
Menu - General [Level 1 - No password required]
Press the back/menu button from the Idle Screen to access the General menu.
Sub-Menu
Setting
Default
Range
(* indicates no configuration; display only)
Description/Notes
Status
AirFlow:
Closed
* (Closed, Open)
Displays the status of the airflow switch.
If Open is displayed, it indicates that the airflow is not detected by the air
pressure switch.
SupplyHighLimit:
Closed
* (Closed, Open)
Displays the status of the high limit contact.
If Open is displayed, it indicates that the humidity level has exceeded the
setpoint on the high limit humidistat.
Interlock:
Closed
* (Closed, Open)
Displays the status of the interlock.
If Open is displayed, it indicates that the humidifier is stopped as a result of
the interlock safety being open.
OccupancyState:
Current value
* (Occupied, Unoccupied, Vacant, Off)
Displays the current occupancy state.
ControlState:
Current value
* (Off, Normal, LowLimit, HighLimit,
NoAirFlow, Interlock)
Displays the current state of the safety control circuit and whether the circuit
has been disconnected due to a safety switch.
BoilerDemand:
Current value
* (min: 0.00%, max: 100.00%)
Displays the measured humidity demand of the humidifier.
PowerOutput:
Current value
* (min: 0.00%, max: 100.00%)
Displays the measured power output of the system as a percentage of the
total power.
ServiceDue:
Off
* (Off, On)
Displays whether the humidifier is due for servicing.
State:
Current value
* (Off, Idle, LineRinse, TankRinse, Filling,
Draining, Heating, Boiling, Alarm)
Displays the current state of operation of the humidifier.
WtrProbeFail:
None
* (None, Capacitive, Resistive, Both)
Displays which one of the water level sensor probes is currently not
functioning properly.
Control
RoomDemand:
Current value
* (min: 0.00%, max: 100.00%)
Displays the room humidity demand value.
(Only appears if ControlProfile is set to an internal control mode or
HumCntrlDemandSrc is set to RoomDemand.)
SupplyHLDemand:
Current value
* (min: 0.00%, max: 100.00%)
Displays the supply high limit humidity demand value.
(Only appears if ModHLProfile is set to an internal control mode or
HumCntrlHLSrc is set to SupplyHLDemand.)
HumDemand:
Current value
* (min: 0.00%, max: 100.00%)
Displays the current humidity demand value.
Physical IO
AirFlow:
Closed
* (Closed, Open)
Displays the status of the airflow switch.
If Open is displayed, it indicates that the airflow is not detected by the air
pressure switch.
SupplyHighLimit:
Closed
* (Closed, Open)
Displays the status of the high limit contact.
If Open is displayed, it indicates that the humidity level has exceeded the
setpoint on the high limit humidistat.
Interlock:
Closed
* (Closed, Open)
Displays the status of the interlock.
If Open is displayed, it indicates that the humidifier is stopped as a result of
the interlock safety being open.
BinExtDemand:
0%
* (0%, 100%)
Displays whether there is currently a humidity demand, when an On/Off
humidifier is used. (Only appears when using an On/Off humidifier.)
ControlInput:
Current value
* (min: 0.00%, max: 100.00%)
Displays the current control input reading.
RoomRH:
Current value
* (min: 0.00%, max: 100.00%)
Displays the room humidity reading value.
(Only appears if ControlProfile is set to InternAnalog or RoomRHSrc is
set to RoomRH.)
SupplyHLRH:
Current value
* (min: 0.00%, max: 100.00%)
Displays the supply high limit humidity reading value.
(Only appears if ModHLProfile is set to InternAnalog or
SupplyHLReadingSrc is set to SupplyHLRH.)

Table of Contents