EasyManua.ls Logo

Neptronic SKE4-E Series - Duct;AHU Control Placement; Control Device Placement in Ducts

Neptronic SKE4-E Series
76 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SKE4-E Steam Humidifier
Installation Instructions and User Manual
www.neptronic.com
Page | - 43 -
Controls Placement (Steam Dispersed into a Duct or AHU)
A typical humidifier control system includes the following along with the humidifier:
x A wall or return duct humidistat
x A high limit duct humidistat
x An airflow switch
Placement of these devices is critical to the proper operation of the overall system.
x The return air humidistat must always be located in the return air duct, in order to ensure
accurate sensing of the air from the humidified space.
x Alternatively, a room humidistat can be used. The room humidistat must be located on an
inside wall or column. It must not be near any discharge air from supply ducts or sources
of heat or cold.
x The airflow switch must be placed in a position capable of accurately opening on a loss of
air flow, in order to prevent the humidifier from running when there is no air to absorb
humidity.
x The high limit humidistat must be positioned far enough, minimum 4.6 m, downstream of
the steam dispersion manifold(s) to prevent over humidification of the duct that could
result in condensation.
x Any device that may be triggered by high humidity levels in close proximity to the steam
dispersion manifold must also be positioned at 4.6 m, downstream of the dispersion
manifold(s).
Return SHC80
Humidity sensor
Or room HRO20
humidistat
SHS80 high limit for constant
flow and VAV application
(or any other device detecting
humidity)
15' minimum
(4.6m)
Air flow switch
Steam dispersion
manifold
Return Air
Fresh Air
Air
Illustration 47 - Controls Placement (Steam Dispersed into a Duct or AHU)

Table of Contents

Related product manuals