Water Supply Connections
x Water Inlet Specifications:
o Inlet water pressure: 1.7 to 4.8 bars
o Maximum temperature: 30°C
o DN15 standard copper water line connection or DN20 PEX pipe line
x Water Supply Line Installation:
o Connect a DN15 water supply braided hose (by others) to the male threaded part
of the pipe.
x In order to facilitate servicing, install a shutoff valve (not supplied) in the water supply line
close to the humidifier.
x It is recommended to install a standard water strainer in the water supply line.
x It is recommended to install a water hammer arrestor, in order to absorb hydraulic shock
and minimize water hammer when the fill valve closes.