SKE4-E Steam Humidifier
Installation Instructions and User Manual
www.neptronic.com
Page | - 54 -
Sub-Menu
Setting
Default
Range
Description/Notes
Extended Config
IdleRinseOn:
Off
Off, On
Select whether to enable automatic rinse cycles while the humidifier is turned on and
ea  Ide  ad-by mode. To select the amount of time the humidifier
remains inactive before a rinse cycle is performed, configure the value of the
IdleRinseInterval setting.
IdleRinseOff:
Off
Off, On
Select whether to enable automatic rinse cycles while the humidifier is turned off and
remains inactive. To select the amount of time the humidifier remains inactive before
a rinse cycle is performed, configure the value of the IdleRinseInterval setting.
WtrAutoCalib:
Always
None, Once, Always
Select the frequency of the auto calibration setting for the water level sensor.
StartupRinse:
Off
Off, On
Select whether to perform an automatic rinse cycle upon each start-up of the humidifier.

Table of Contents