Stainless steelEnamelCopperOther information 3x400 V
Water heater
240litreVolume total
70litreVolume boiler section
170litreVolume, hot water heater
1.0/10MPa/barMax pressure in hot water heat-
er
Stainless steelEnamelCopperCorrosion protection
Capacity hot water heating according to EN 16 147
6
281litreTap volume 40 °C at Normal
comfort (V
max
)
2.8COP at Normal comfort (COP
t
)
54WIdle loss at Normal comfort (P
es
)
Dimensions and weight
600mmWidth
616mmDepth
2100-2125mmHeight
2270mmRequired ceiling height
195205202kgWeight
066 045066 043066 013Part No.
1
A20(12)W35, exhaust air flow 200 m
3
/h
2
A20(12)W45, exhaust air flow 150 m
3
/h
3
A20(12)W55, exhaust air flow 110 m
3
/h
4
The value varies with the selected fan curve. For more
extensive sound data including sound to channels visit
www.nibe.eu.
5
The value may vary with the room's damping capacity.
These values apply with a damping of 4 dB.
6
A20(12) exhaust air flow 150 m
3
/h
65Chapter 12 | Technical dataNIBE™ F370