Hoses must be in good condition and be equipped with
leak proof quick-couplings. Before using the collecting
machine, check that it works correctly and has been
well maintained, and that corresponding electrical
components are sealed, to prevent ignition if any refri-
gerant should come out. Contact the manufacturer in
the event of any doubts.
Return the collected refrigerant to the refrigerant
supplier in the correct collection container and with
the relevant Waste Transfer Note. Do not mix refriger-
ants in collection devices or containers.
If compressors/compressor oil are/is to be removed
ensure that the affected device is drained to an accept-
able level to ensure that no combustible refrigerant
remains in the lubricant. Compressors must be drained
before being returned to the supplier. Only electrical
heating of the compressor housing may be used to
quicken draining. Drain oil from the system in a safe
manner.
Serial number
Serial number
The serial number can be found at the bottom right of
the front cover and in the info menu (menu 3.1).
Serial number
Caution
Always give the product's serial number (14
digits) when reporting a fault.
Country specific information
Installer manual
This installer manual must be left with the customer.
5Chapter 1 | Important informationNIBE™ F370

Other manuals for Nibe F370

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Nibe F370 and is the answer not in the manual?

Nibe F370 Specifications

General IconGeneral
TypeExhaust Air Heat Pump
RefrigerantR290
Energy classA++
Energy Efficiency Class (Space Heating, 35°C)A++
Energy Efficiency Class (Space Heating, 55°C)A+
ApplicationResidential
Hot Water Tank Volume170 l
Heating Power8.5 kW