start delta-T, stop delta-T: Here you can set the tem-
perature difference between solar panel and solar tank
at which the circulation pump is to start and stop.
max. tank temperature, max. solar collector temp.:
Here you can set the maximum temperatures in tank
respectively solar panel at which the circulation pump
is to stop. This is to protect against excess temperatures
in the solar tank.
max solar pool temperature: Here you can set the
maximum temperature where the solar panel stops
heating pool (if the unit is made up in such a way). Pool
heating can only occur if there is a heat surplus when
heating and/or the hot water demand is met.
If the unit has an anti-freeze function and/or solar
panel cooling you can activate them here. When the
function has been activated, you can make settings for
them.
freeze protection
anti-freeze temperatur e: Here you can set the temper-
ature in the solar panel at which the circulation pump
is to start to prevent freezing.
solar panel cooling
start solar collector cooling: If the temperature in the
solar panel is greater than this setting at the same time
that the temperature in the solar tank is greater than
the set maximum temperature, the external function
for cooling is activated.
Menu 5.3.7 - external addition
Make settings for external addition here. External addi-
tion is for example external oil, gas or electric boiler.
If the external addition is not step controlled, in addi-
tion to selecting when this should start also set the run
time for the addition.
If the external addition is step controlled you can select
when the addition is to start, set the maximum number
of permitted steps and whether binary stepping is to
be used.
See the accessory installation instructions for function
description.
Menu 5.4 - soft in/outputs
Here you can select which in/output on the input circuit
board (AA3) the external contact function (page 26)
is to be connected to.
Selectable inputs on terminal block AUX1-5 (AA3-X6:9-
18) and output AA3-X7 (on the input circuit board).
Menu 5.5 - factory setting service
All settings can be reset (including settings available
to the user) to default values here.
NOTE
When resetting, the start guide is displayed
the next time the indoor module is restarted.
Menu 5.6 - forced control
You can force control the different components in the
indoor module and any connected accessories here.
Menu 5.7 - start guide
When the indoor module is started for the first time
the start guide starts automatically. Start it manually
here.
See page 31 for more information about the start
guide.
Menu 5.8 - quick start
It is possible to start the compressor from here.
Caution
There must be a heating or hot water demand
to start the compressor.
Caution
Do not quick start the compressor too many
times in succession over a short period of time
as this may damage the compressor and its
ancillary equipment.
Menu 5.9 - floor drying function
length of period 1 - 3, 5-7
Setting range: 0 - 30 days
Default value: 2 days
temp. period 1 - 3, 5-7
Setting range: 15 - 70 °C
Default value:
20 °Ctemp. period 1
30 °Ctemp. period 2
40 °Ctemp. period 3
40 °Ctemp. period 5
30 °Ctemp. period 6
20 °Ctemp. period 7
length of period 4
Setting range: 0 - 30 days
Default value: 3 days
temp. period 4
Setting range: 15 - 70 °C
Default value: 45 °C
Set the function for under floor drying here.
You can set up to seven period times with different
calculated flow temperatures. If less than seven periods
are to be used, set the remaining period times to 0
days.
Mark the active window to activate the under floor
drying function. A counter at the bottom shows the
number of days the function has been active.
53Chapter 8 | Control - MenusNIBE™ VVM 310