CAUTION!
Risk of damage to the gear clamp.
Do not over-tighten the gear clamp. The maximum torque value for gear clamps is 16 in·lbs
(180 N·cm).
– Do not combine multiple steam lines, except at the steam distributor. Use a Nortec adaptor specically
designed for that purpose, and only if the humidiers connected to the adaptor operate in parallel.
– To minimize formation of condensation, the steam pipe must be insulated with a minimum of 1 in
(25 mm) of pipe insulation over its entire length.
– The weight of the steam pipe must be supported so there is no load on the humidier.
WARNING!
Risk of severe burns from contact with hot steam vapors!
Restrictions in the cross-section of the steam line will cause excessive backpressure in the
steam tank when the unit is operating, which may cause unexpected release of hot steam va-
pors. Bare skin exposed to the hot steam vapors can result in severe burns. In addition, excess
backpressure also affects performance of the unit.
Prevention: Observe the following:
• Upon completion of the installation, purge the steam line to remove any contaminants and
installation materials.
• The steam hose (if used) must not have any kinks or other restrictions.
• To prevent condensate pockets, the steam line must not sag. If necessary, support the steam
line with pipe clamps, trough, or wall brackets, and install a condensate drain at the lowest
point in the steam line.
• DO NOT install a shutoff valve (e.g. a manually operated shutoff valve, solenoid valve, etc.)
in the steam line.
Table 13: Equivalent Length of Typical Steam Line Fittings
Nominal Tube
Size
Standard 90°
Elbow
Standard 45°
Elbow
Side-Outlet Tee
1.75 in (45 mm) 3.5 ft (1.1 m) 1.75 ft (0.5 m) 7 ft (2.1 m)
3 in (75 mm) 5 ft (1.5 m) 2.5 ft (0.8 m) 11 ft (3.4 m)
4 in (100 mm) 8 ft (2.4 m) 4 ft (1.2 m) 15 ft (4.6 m)
Figure 13:
Minimum Upslope 10
o
Minimum Downslope 2
o
Min.
300 mm
300 mm
Min.
300 mm
300 mm
Minimum
Downslope
1.2
o
Steam Line Condensate Drain Line
12 in
(300 mm)
2 in
(50 mm)
12 in
(300 mm)
½ in
(12 mm)
1 in
(25 mm)
48 in
(1.2 m)
1 in
(25 mm)
48 in
(1.2 m)
Minimum
Downslope
1.2