52 Installation
2583703_EN_1608 Nortec GS
5.9.4 Gas Connection Checklist
Check the following to ensure that the gas connection for the humidier has been installed correctly:
Certied manual gas shutoff valve installed immediately upstream from the humidier?
Sediment trap installed (if using black pipe)?
Stainless steel section of pipe installed at the gas connection to the humidier?
Gas pipe routing allow clear access to other service connections at humidier?
Gas piping adequately supported?
Gas leakage test completed, and all leaks xed?
De-pressurize gas supply line after leak test?