5.8.2 Exhaust Vent Installation (CS/NX Model)
The Nortec GS (CS/NX model) humidier must be installed as a Category IV fan-assisted gas appliance.
In addition to the specic requirements described in "Installation as a Category IV Appliance" on page 48, refer
to the general requirements – "General Requirements" on page 43.
All vent installations must be in accordance with national and the local regulations.
The exhaust outlet on the unit has a female connection (metric). Each unit is supplied with a metric to
imperial adaptor (with internal gaskets) to accomodate imperial vent sizes.
To connect the exhaust vent, rst insert the adaptor into the exhaust outlet and secure it to the top panel
with four sheetmetal screws (supplied) – refer to Figure 22. Then slide the exhaust vent into the adaptor
until it bottoms out, and secure it with the clamp built into the adaptor. A sealant is not required.
Make sure that the exhaust vent is supported by hangers or pipe straps so that there is no load on the
humidier.
Figure 22:
1
2
3
4
Nortec GS Exhaust Vent Connection (CS/NX Model Only)
1 Vent, exhaust – CPVC or type BH (CPVC only for GS 50-CS/NX)
2 Adaptor, exhaust – plastic (supplied)
3 Screw, sheetmetal (×4, supplied)
4 Outlet, humidier exhaust