46 Installation
2583703_EN_1608 Nortec GS
Figure 21:
3 ft 1 m) min.
1
2
3
4
5
6
7
8
9
2 ft (610 mm) min.
Horizontal Venting (with Optional Sealed Combustion Hookup) – Category IV
1 Terminal, exhaust ("Tee")
2 Terminal, air intake (90° elbow) – pointed down, for optional sealed combustion hookup
3 Outlet, exhaust outlet
4 Inlet, air intake
5 Vent, air intake – for optional sealed combustion horizontal hookup
6 Drain, condensate (with trap) – minimum 12 in (300 mm) trap height, and connected to oor drain or condensate pump
7 "Tee", condensate
8 Hanger
9 Vent, exhaust, BH type – plastic or stainless steel. All joints air and water-tight. Full condensate "Tee" with condensate port and trap.