Gas Connection
Certied manual gas shutoff valve installed immediately upstream from the humidier?
Sediment trap installed (if using black pipe)?
Stainless steel section of pipe installed at the gas connection to the humidier?
Gas pipe routing allow clear access to other service connections at humidier?
Gas piping adequately supported?
Gas leakage test completed, and all leaks xed?
De-pressurize gas supply line after leak test?
Electrical Connections
Power supply meet the rated current draw limits shown on the specication label (Figure 3 on page 10)?
Power supply have an external dedicated fused disconnect switch?
All wiring done according to the wiring diagram and instructions in this manual?
Main power cable proper grounding through the ground lug inside the electric cabinet?
All cables fastened securely?
All cables free of tension and pass through cable glands or grommets?
Electrical installation meet the applicable national and local codes?
All access panels closed and fastened securely?