CHARGER / DISCAHRGER UL10 OPERATION MAUNAL
20 © NorTec Electronics 2014
6.4.3 Printing Programs
6.4.3.1
General
By hitting the key P the last printout appears in the main menu or in the submenu in the PP mode.
6.4.3.2 Program Р: printer and measurements of voltages of individual batteries
The Program Р is a special program serving to print out the protocol while another program is run-
ning, in particular when measuring and registering voltages of individual batteries. The following op-
tions are available:
- Automatic protocol print-out in the program
- Manual protocol print-out in the program
NOTE: Automatic protocol print-out is possible only when the cable is available to measure
voltages of individual batteries (optional).
DATA OF ALL PRINT-OUT PARAMETERS
The capacity data in % relate to the battery nominal capacity.
The line TEMPERATURE is printed out only when both temperature sensors are connected. The
reading relates to a battery with a higher temperature.
INSTRUCTIONS HOW TO MEASURE VOLTAGES OF INDIVIDUAL BATTERIES
In the program х type of batteries 20.
The voltages of individual batteries are possible to measure only in the manual protocol print-out
mode is indicated by a short beep. At this moment it is possible to measure voltage with the measur-
ing cable and to print out voltages of individual batteries. The maximum number of batteries is 99.
If during voltage measurement a beep sounds the measurement should be repeated. The counting
of cells is continued only providing the measurement is correct. The voltage of a battery is displayed
and printed out simultaneously.
If the sign * is printed before the relevant battery voltage it means that it is less than 1.55 V (the vol-
tage at the end of charging of an individual nickel-cadmium battery). If the measurement is made at
a proper moment of time (according to the requirement of the battery manufacturer) the 1.55 V may
prove that the battery is faulty.
If individual batteries are not measured the lines CELL 01 – CELL # are not printed. In case the pro-
gram print-out does not respond to the data input the device receives a repeated inquiry after 30
seconds, etc., and resumes the normal program run mode.