7.7 Program 110. Commissioning – air-tight aircraft lead acid battery
Stage name Maximum
duration
Program number 110
Operation number 1
Operation type Commissioning
Battery type Lead acid
Manufacturing process Gel / absorbed electrolyte
Access to valves unavailable
Battery type 10
Minimum battery capacity 2 Ah
Maximum battery capacity 200 Ah
Minimum battery voltage 2 V
Maximum battery voltage 30 V
Maximum number of batteries 15
Stage 1 (S1) Discharge Discharge current а =xС (A) x= 0.2
Stage 1 (S1) Discharge Discharge depth V/battery 1,5
Discharge voltage <1.5 V Error
Message
Use program
410
Stage 2 (S2) I-Charge Current = xС (A) x= 0.4 8h
Stage 2 (S2) I-Charge Umax = V/battery 2.4 8h
Stage 3 (S3) U-Charge Umax = V/battery 2.4 8h
Stage 3 (S3) U-Charge Ia = xС (A) x= 0.04 8h
Note: when the maximum output current of the device is exceeded the maximum time para-
meters change accordingly.