7.19 Program 411. Maintenance – Pb battery sealed commercial
Stage name Maximum
duration
Program number 411
Operation number 4
Operation type Maintenance
Battery type Lead acid
Manufacturing process Gel / absorbed electrolyte
Access to valves Unavailable
Battery type 11
Minimum battery capacity 2 Ah
Maximum battery capacity 200 Ah
Minimum battery voltage 2
Maximum battery voltage 30
Maximum number of batteries 15
Stage 1 (S1) Discharge Discharge current 0.2 6 h
а = xС (A)
Stage 1 (S1) Discharge Discharge depth 1.5 6 h
V/battery
Stage 2 (S2) Precharge Voltage charging 2.4 2 h
Umax = V/battery
Stage 2 (S2) Precharge Current = xС (A) Х= 0.36 2 h
Stage 3 (S3) I-Charge 1 Current = xС (A) 0.36 6 h
Stage 3 (S3) I-Charge 1 Umax = V/battery 2.4 6 h
Stage 4 (S4) U-Charge 1 Umax = V/battery 2.4 6 h
Stage 4 (S4) U-Charge 1 I а= xС (A) 0.02 6 h
Stage 4 (S4) U-Charge 1 Umax = V/battery 2.4 2 h
Stage 5 (S5) Discharge Discharge current 0.2 6 h
а = xС (A)
Stage 5 (S5) Discharge Discharge depth 1.5 6 h
V/battery
Stage 6 (S6) I-Charge 2 Current = xС (A) 0.36 6 h
Stage 6 (S6) I-Charge 2 Umax = V/battery 2.4 6 h
Stage 7 (S7) U-Charge 2 Umax = V/battery 2.4 6 h
Stage 7 (S7) U-Charge 2 I а= xС (A) 0.02 6 h
Stage 7 (S7) U-Charge 2 Umax = V/battery 2.4 2 h
Note: the program is identical to program 311