CHARGER / DISCAHRGER UL10 OPERATION MAUNAL
© NorTec Electronics 2014
45
7.9 Program 116. Commissioning – Pb battery vented commercial
Stage name Maximum
duration
Program number 116
Operation number 1
Operation type Commissioning
Battery type Lead acid
Manufacturing process Liquid electrolyte
Access to valves open
Battery type 16
Minimum battery capacity 10 Ah
Maximum battery capacity 400 Ah
Minimum battery voltage 2 V
Maximum battery voltage 30 V
Maximum number of batteries 15
Stage 1 (S1) Discharge The electrolyte is filled 20 min or
Enter
Stage 2 (S2) Discharge Discharge current а =xС (A) 0.2
Stage 2 (S2) Discharge Discharge depth V/battery 1.5
Stage 2 (S2) Voltage < 1,5 V Error
message.
Use program
416!
Stage 3 (S3) I-Charge Current = xС (A) Х= 0.2 8µ
Stage 3 (S3) I-Charge Umax = V/battery 2.4 8µ
Stage 4 (S4) U-Charge Umax = V/battery 2.4 8µ
Stage 4 (S4) U-Charge Ia = xС (A) x= 0.04 8µ
Note: when the maximum output current of the device is exceeded the maximum time para-
meters change accordingly.