Introduction iTrans Fixed Point Single/Dual Gas Monitor
1-6 iTrans User Manual (P/N: 77023554-1)
1.4. Special Instructions for Safe Use (EU)
Cable connection: The cable entry device shall be of a certified flameproof
type, suitable for the conditions of use and correctly installed.
Conduit Connection: An Ex d certified sealing device, such as, a conduit
seal with setting compound, suitable for the conditions of use, and correctly
installed, shall be provided immediately to the entrance of the housing.
Unused openings: Unused openings shall be closed with suitable Ex d
certified closing elements.
Dual Onboard: The “Y” adapter parts used to assemble dual onboard
configurations do not have Atex approval. Consult factory for dual onboard
Atex options.