A-21
Appendices
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
A-4 Inverter Parameter List
App
3013
hex
6B
hex
1344 hex Window Comparator
FI Hysteresis Width
b065 RW 0. to 10.
(Upper limit: (b063 b064) / 2)
1 [%] Possible
3013
hex
70
hex
1349 hex
Analog Operation Level
at FV Disconnection
b070 RW 0 to 100/255 (no) 1 [%] Possible
(TxPDO)
3013
hex
71
hex
134A
hex
Analog Operation
Level at FI
Disconnection
b071 RW 0 to 100/255 (no) 1 [%] Possible
(TxPDO)
3013
hex
75
hex
134E
hex
Ambient Temperature b075 RW 10 to 50 1 [C] Possible
3013
hex
78
hex
1351 hex Integrated Power Clear b078 RW 00: Disabled
01: Clear (Return to 00 after clear)
Possible
3013
hex
79
hex
1352 hex Integrated Power
Display Scale
b079 RW 1 to 1000 1 Possible
3013
hex
7C
hex
1355 hex Starting Frequency b082 RW 10 to 999 (10000) 0.01 [Hz] Possible
(TxPDO)
3013
hex
7D
hex
1356 hex Carrier Frequency b083 RW 20 to 150 0.1 [kHz] Possible
(TxPDO)
3013
hex
7E
hex
1357 hex Initialization Selection b084 RW 00: Initialization disabled
01: Clear fault monitor
02: Initialize data
03: Clear fault monitor + initialize
data
04: Do not set.
Possible
(TxPDO)
3013
hex
7F
hex
1358 hex Initialization Data
Selection
b085 RW 00: Do not change. Possible
(TxPDO)
3013
hex
80
hex
1359 hex Frequency Conversion
Coefficient
b086 RW 1 to 9999 0.01 Possible
3013
hex
81
hex
135A
hex
STOP Key Selection b087 RW 00: Enabled
01: Disabled
02: Only reset is enabled
Possible
(TxPDO)
3013
hex
82
hex
135B
hex
Free-run Stop
Selection
b088 RW 00: 0 Hz restart
01: Frequency matching restart
0
2: Fre
quency pull-in restart
Possible
(TxPDO)
3013
hex
83
hex
135C
hex
Automatic Carrier
Reduction
b089 RW 00: Disabled
01: Enabled, depends on the
current
02: Enabled, depends on the fin
temperature
Possible
(TxPDO)
3013
hex
84
hex
135D
hex
Usage Rate of
Regenerative Braking
b090 RW 0 to 1000 0.1 [%] Possible
(TxPDO)
3013
hex
85
hex
135E
hex
Stop Selection b091 RW 00: Deceleration stop
01: Free-run stop
Possible
(TxPDO)
3013
hex
86
hex
135F hex Cooling Fan Operation b092 RW 00: Always
01: Only during operation
(Including 5 minutes after the
power is turned on and also
after the inverter stops)
02: Depends on the fin temperature
Possible
(TxPDO)
3013
hex
87
hex
1360 hex Cooling Fan Total
Operating Time Clear
b093 RW 00: Operating time count
01: Clear (Return to 00 after clear)
Possible
(TxPDO)
3013
hex
88
hex
1361 hex Initialization Target
Selection
b094 RW 00: All data
01: Data other than
terminal/communications
02: U*** registration function only
03: Other than U*** registration
function
Possible
(TxPDO)
3013
hex
89
hex
1362 hex Regenerative Braking
Selection
b095 RW 00: Disabled
01: Enabled (Disabled during stop)
02: Enabled (Enabled during stop)
Possible
(TxPDO)
3013
hex
8A
hex
1363 hex Regenerative Braking
ON Level
b096
RW 330 to
380/660 to 760 1 [V] Possible
(TxPDO)
3013
hex
8E
hex
1367 hex Free V/f Frequency 1 b100 RW 0 to Free V/f Frequency 2 1 [Hz] Possible
(TxPDO)
3013
hex
8F
hex
1368 hex Free V/f Voltage 1 b101 RW 0 to 8000 0.1 [V] Possible
(TxPDO)
3013
hex
90
hex
1369 hex Free V/f Frequency 2 b102 RW 0 to Free V/f Frequency 3 1 [Hz] Possible
(TxPDO)
3013
hex
91
hex
136A
hex
Free V/f Voltage 2 b103 RW 0 to 8000 0.1 [V] Possible
(TxPDO)
Index
Sub-
index
Register
No.
Function name
Parameter
No.
R/W Monitor and setting items
Data
resolution
PDO
map