EasyManuals Logo

Omron 3G3M1-A4004-ECT User Manual

Omron 3G3M1-A4004-ECT
850 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #45 background imageLoading...
Page #45 background image
*4. When Carrier Frequency (3004Hex-1BHex) is set to the following or below, derating is required.
HHD mode...A2001 to A2037: 8 kHz, A2055 to A2185: 10 kHz
HND mode...A2001 to A2037: 4 kHz, A2055 to A2150: 10 kHz, A2185: 4 kHz
For derating, refer to A-1 Derating Table on page A-2.
*5.
The following shows the calculated value when the power supply capacity is 500 kVA (10x the inverter ca-
pacity when the inverter capacity exceeds 50 kVA) and when a %X = 5% power supply is connected.
*6. The numeric value is the average braking torque per individual motor. (Varies according to motor efficiency)
*7. Allowable ambient temperature of 40°C or below of A2022 to A2037 in the HND mode.
The rated output current in the HND mode decreases by 1% for every temperature increase of 1°C when
the ambient temperature is 40°C or more.
Three-phase 400-V Class
HHD/HD: Heavy load, HND/ND: Light load
Item Three-phase 400 V
Model
(3G3M1-A4â–¡â–¡â–¡-ECT)
004 007 015 022 030 040 055 075 110 150 185 220
Maxi-
mum
applica-
ble mo-
tor ca-
pacity
*1
kW HD 0.75 1.1 2.2 3 4 5.5 7.5 11 15 18.5 22 30
ND 0.75 1.5 2.2 3 4 5.5 11 15 18.5 22 30 37
HHD 0.4 0.75 1.5 2.2 3 4 5.5 7.5 11 15 18.5 22
HND
0.75 1.1 2.2
3
*7
4
5.5
*7
7.5 11 15 18.5 22 30
HP HD 1 1 1/2 3 4 5 7 1/2 10 15 20 25 30 40
ND 1 1 1/2 3 4 5 7 1/2 15 20 25 30 40 50
HHD 1/2 1 1 1/2 3 4 5 7 1/2 10 15 20 25 30
HND 1 1 1/2 3 4 5 7 1/2 10 15 20 25 30 40
Rated
output
capacity
[kV
A]
*2
380
V
HD
1.2 2.2 3.3 4.1 5.8 7.3 12 15 20 25 30 39
ND 1.4 2.7 3.6 4.5 6.1 7.9 14 19 24 29 39 47
HHD 1.2 2.2 3.2 3.6 4.7 6.1 9.7 12 16 20 26 30
HND 1.4 2.7 3.6 4.5 5.8 7.3 12 15 20 25 30 39
480
V
HD 1.5 2.8 4.2 5.2 7.3 9.2 15 19 26 32 37 50
ND 1.7 3.4 4.6 5.7 7.6 10 18 24 31 37 49 60
HHD 1.5 2.8 4 4.6 6 7.6 12.3 15 20 26 32 37
HND 1.7 3.4 4.6 5.7 7.3 9.2 15 19 26 32 37 50
Rated input voltage
*3
Three-phase 380 to 480V, 50/60 Hz
Rated input
current [A]
*4
HD 2.7 3.9 7.3 11.3 14.2 16.8 23.2 33 43.8 52.3 60.6 77.9
ND 2.7 4.8 7.3 11.3 14.2 16.8 33 43.8 52.3 60.6 77.9 94.3
HHD 1.7 3.1 5.9 8.2 11.3 14.2 17.3 23.2 33 43.8 52.3 60.6
HND 2.7 3.9 7.3 11.3 14.2 16.8 23.2 33 43.8 52.3 60.6 77.9
Rated output voltage Three-phase 380 to 480V (with AVR)
Rated output
current [A]
*5
HD 1.8 3.4 5 6.3 8.8 11.1 17.5 23 31 38 45 60
ND 2.1 4.1 5.5 6.9 9.2 12 21.5 28.5 37 44 59 72
HHD 1.8 3.4 4.8 5.5 7.2 9.2 14.8 18 24 31 39 45
HND
2.1 4.1 5.5
6.9
*7
8.8
11.1
*7
17.5 23 31 38 45 60
1 Overview
1-11
M1 Series EtherCAT Type User’s Manual (I670)
1-3 Specifications
1
1-3-1 Standard Specifications

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron 3G3M1-A4004-ECT and is the answer not in the manual?

Omron 3G3M1-A4004-ECT Specifications