Index
(hex)
Sub-
index
(hex)
Pa-
rame-
ter No.
Function name Monitor or data range
Default
data
Set-
ting
dur-
ing
RUN
Unit
PDO
map
13 Z18 Second Last
Alarm Info. Run-
ning Status 3
V/f DTV
PG V/f PG DTV
SLV PGV
PM SLV PM PGV
0000 to FFFF hex
Bit 15: ---
Bit 14: OL (Overload warning)
Bit 13: LOC (Light load detection)
Bit 12: OL2 (Overload warning 2)
Bit 11: OLP (During active drive)
Bit 10: LIFE (Life warning)
Bit 9: OHF (Fin Overheat warning)
Bit 8: TRY (During retry)
Bit 7: FAN (Fan operation signal)
Bit 6: Reserved
Bit 5: THM (Thermal warning)
Bit 4: IPF (During restart after instan-
taneous power failure)
Bit 3: SETM (2nd motor selection)
Bit 2: IRDY (Operation ready)
Bit 1: FDT1 (Over set Frequency ar-
rival)
Bit 0: FAR1 (Constant speed arrival)
0 --- --- Possible
(TxPDO)
29 Z40 1st Cumulative
Run Time
V/f DTV
PG V/f PG DTV
SLV PGV
PM SLV PM PGV
0 to 65,535
0 --- 10 h Possible
(TxPDO)
2A Z41 2nd Cumulative
Run Time of mo-
tor
2D
Z44 2nd Number of
Startups
V/f DTV
PG V/f PG DTV
SLV PGV
PM SLV PM PGV
0 to 65,535
0 --- --- Possible
(TxPDO)
33 Z50 Third Last Alarm
Info. Output Fre-
quency
V/f DTV
PG V/f PG DTV
SLV PGV
PM SLV PM PGV
0.00 to 655.35
0 --- Hz Possible
(TxPDO)
34 Z51 Third last Alarm
info. Output Cur-
rent
V/f DTV
PG V/f PG DTV
SLV PGV
PM SLV PM PGV
0.00 to 655.35
0 --- A Possible
(TxPDO)
35 Z52 Third last Alarm
info. Output V
olt-
age
V/f DTV
PG V/f PG DTV
SLV PGV
PM SLV PM PGV
0 to 1,000
0 --- V Possible
(TxPDO)
36 Z53 Third Last Alarm
Info. Torque
Monitor
V/f DTV
PG V/f PG DTV
SLV PGV
PM SLV PM PGV
-999 to 999
0 --- % Possible
(TxPDO)
Appendices
A-79
M1 Series EtherCAT Type User’s Manual (I670)
A-4 Lists of Manufacturer Specific Objects 2
(Inverter Parameters)
A
A-4-3 Z Group Parameter List (Alarm Information 1)