(hex)
Sub-
index
(hex)
Pa-
rame-
ter No.
Function name Monitor or data range
Default
data
Set-
ting
dur-
ing
RUN
Unit
PDO
map
0A H09 Starting Mode
Auto Search
Function Selec-
tion
V/f DTV
PG V/f PG DTV
SLV PGV
PM SLV PM PGV
0: Disable
1: Enable only at restart after mo-
mentary power failure
2: Enable at normal start and restart
after momentary power failure
0 --- --- Possible
0C H11 Stop Selection
V/f DTV
PG V/f PG DTV
SLV PGV
PM SLV PM PGV
0: Deceleration stop
1: Free run stop
0
--- Possible
0D H12 Instantaneous
Overcurrent Lim-
iting Function Se-
lection
V/f DTV
PG V/f PG DTV
SLV PGV
PM SLV PM PGV
0: Disable
1: Enable
1
--- Possible
0E H13 Power Interrup-
tion Restart Wait
Time
V/f DTV
PG V/f PG DTV
SLV PGV
PM SLV PM PGV
0.1 to 100.0
0.5
s Possible
0F H14 Deceleration Set-
ting During Cur-
rent Limit for Re-
start Mode after
Power Interrup-
tion
V/f DTV
PG V/f PG DTV
SLV PGV
PM SLV PM PGV
0.00: Selected deceleration time
0.01 to 100.00
999: According to current limiter
*1
999
Hz/s Possible
10 H15 Continuous Run-
ning Voltage Lev-
el
V/f DTV
PG V/f PG DTV
SLV PGV
PM SLV PM PGV
200 to 300 (200 V class series)
400 to 600 (400 V class series)
235
V Possible
11 H16 Allowable Time
for Power Inter-
ruption Restart
V/f DTV
PG V/f PG DTV
SLV PGV
PM SLV PM PGV
0.0 to 30.0
999: Auto judgment
*1
999
s Possible
13 H18 Torque Control
Operate Selec-
tion
V/f DTV
PG V/f PG DTV
SLV PGV
PM SLV PM PGV
0: Disable (Speed control)
2: Torque current command input
3: T
orque command input
0 --- --- Possible