(6) The value of Torque Boost
V
oltage (3004-0A hex, 3009-06
hex) is too high.
Check and readjust the value of
Torque Boost Voltage (3004-0A
hex, 3009-06 hex) so that lower-
ing the value does not cause a
stall.
→ Adjust the value of Torque
Boost Voltage (3004-0A hex,
3009-06 hex).
Set the value of Torque Boost
Voltage (3004-0A hex, 3009-06
hex) appropriately.
(7) The V/f settings are incorrect. Check that the 1st Base
Frequency (3004-05 hex) and
1st rated voltage at base
frequency (3004-06 hex) match
the values on the motor rating
nameplate.
→ Match the data to the value on
the motor rating nameplate.
Configure the V/f settings appro-
priately.
(8) There is an incorrect parame-
ter setting.
The function of
1st Thermistor
mode selection (3008-1B hex)
is enabled even though the PTC
thermistor is not used.
→ Change the setting of 1st
Thermistor mode selection
(3008-1B hex) to 0 (Disable).
Set 1st Thermistor mode
selection (3008-1B hex) appro-
priately.
Attached in-
formation
None
Precautions/
Remarks
None
Appendices
A-256
M1 Series EtherCAT Type User’s Manual (I670)