Event name Motor Overload Warning Event code 68460000 hex
Meaning The current value reached the overload warning level.
Source EtherCAT Master Function Mod-
ule
Source details Slave Detection tim-
ing
Continuously
Error attrib-
utes
Level Observation Recovery Automatic re-
covery
Log category System log
Effects User program Continues. Operation Not affected.
Indicators EtherCAT NET RUN EtherCAT NET ERR EtherCAT LINK/ACT
--- --- ---
System-de-
fined varia-
bles
Variable Data type Name
None None None
Cause and
correction
Assumed cause Correction Prevention
(1) Motor overload warning → Check if the current flow is
more than the current value set
in 1st Overload Early W
arning
Detection Level
(3005-26 hex),
2nd Overload Warning
Detection Level (3005-38 hex),
and Overload early warning 2
Level (3005-23 hex).
Set 1st Overload Early Warning
Detection Level (3005-26 hex),
2nd Overload Warning
Detection Level (3005-38 hex),
and Overload early warning 2
Level (3005-23 hex) appropriate-
ly.
Attached in-
formation
None
Precautions/
Remarks
None
Appendices
A-277
M1 Series EtherCAT Type User’s Manual (I670)
A-5 Sysmac Error Status Codes
A
A-5-2 Error Descriptions

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron 3G3M1-A4004-ECT and is the answer not in the manual?

Omron 3G3M1-A4004-ECT Specifications

General IconGeneral
BrandOmron
Model3G3M1-A4004-ECT
CategoryInverter
LanguageEnglish

Related product manuals