Power
supply
line
Standard applicable
motor (kW)
Inverter model Specifications Fuse rating (A)
Three-
phase 400
V
18.5 3G3M1-A4110-ECT ND 125 (IEC 60269-4)
3G3M1-A4150-ECT HND 160 (IEC 60269-4)
HD
3G3M1-A4185-ECT HHD 160 (IEC 60269-4)
22 3G3M1-A4150-ECT ND 160 (IEC 60269-4)
3G3M1-A4185-ECT HND 160 (IEC 60269-4)
HD
3G3M1-A4220-ECT HHD 200 (IEC 60269-4)
30 3G3M1-A4185-ECT ND 160 (IEC 60269-4)
3G3M1-A4220-ECT HND 200 (IEC 60269-4)
HD
37 ND
Single-
phase 200
V
0.1 3G3M1-AB001-ECT HHD 50 (IEC 60269-4)
0.2 HND
3G3M1-AB002-ECT HHD 50 (IEC 60269-4)
0.4 HND
3G3M1-AB004-ECT HHD 50 (IEC 60269-4)
0.55 HND
0.75 3G3M1-AB007-ECT HHD 50 (IEC 60269-4)
1.1 HND
1.5 3G3M1-AB015-ECT HHD 125 (IEC 60269-4)
2.2 HND
3G3M1-AB022-ECT HHD 125 (IEC 60269-4)
3 HND
3.7 3G3M1-AB037-ECT HHD 160 (IEC 60269-4)
Disconnect
Cutter
MC
Inverter
L1/R
L2/S
L3/T
R
0
T0
MCCB
RCD/ELCB, etc,
Power
supply
Power
supply
or
Use a molded case circuit breaker (MCCB), residual current device (RCD) or earth leakage
circuit breaker (ELCB), and magnetic contactor (MC) that are compliance with EN or IEC
Standards.
When using a residual current device (RCD) or earth leakage circuit breaker (ELCB) as
protection against electric shock through direct or indirect contact with the power line or
node, be sure to install a RCD or ELCB of type B (DC capable) model on the input side
(primary side) of the inverter.
2 Design
2-73
M1 Series EtherCAT Type User’s Manual (I670)
2-4 Others
2
2-4-1 Compliance with EU Directives and UKCA