Power supply line
Standard applicable motor (kW)
Inverter model
Specifications
Molded
case circuit
breaker
(MCCB) or
earth leak-
age circuit
breaker
(RCD/
ELCB) rat-
ed current
*1
Recommended wire size (mm
2
)
For main circuit
For control circuit terminal
Control power supply auxiliary input R0, T0
Main power
supply in-
put [L1/R,
L2/S, L3/
T]
*2
Inverter
ground
[
]
*2*3
Inverter output [U, V, W]
*2
For DC reactor connection [P1, P(+)]
For braking resistor connection [P(+), DB]
*2
With DC reactor
Without DC reactor
With DC reactor
Without DC reactor
With DC reactor
Without DC reactor
Three-
phase
400 V
11 3G3M1-
A4055-ECT
ND 30 50 4 6 4 6 4 4 2.5 0.75 -
3G3M1-
A4075-ECT
HND
HD
3G3M1-
A41
10-ECT
HHD 10 10
15
3G3M1-
A4075-ECT
ND 40 69 6 6 6 10
3G3M1-
A4110-ECT
HND
HD
3G3M1-
A4150-ECT
HHD
18.5
3G3M1-
A41
10-ECT
ND 75
10 16 10 16 10
3G3M1-
A4150-ECT
HND
HD
3G3M1-
A4185-ECT
HHD 2.5
22 3G3M1-
A4075-ECT
ND 50 100 16 -
3G3M1-
A4185-ECT
HND 2.5
HD
3G3M1-
A4220-ECT
HHD
30 3G3M1-
A4185-ECT
ND 75 125 16 25 16 16 25
3G3M1-
A4220-ECT
HND
HD
37 ND 100 25 35 25
*1. The frame size and model of MCCB, RCD or ELCB (with overcurrent protection function) change according to the ca-
pacity of the power transformer. For details on selection method, refer to related technical data.
*2.
The recommended size of wire to the main circuit terminal is the size when PVC wire having an allowable temperature
of 70°C and a rated voltage of 600 V is used, and the ambient temperature is 40°C.
*3. Only one wire of recommended size can be connected to the ground terminal.
2 Design
2-80
M1 Series EtherCAT Type User’s Manual (I670)

Table of Contents

Related product manuals