EasyManua.ls Logo

Omron 3G3M1-A4110-ECT - Page 559

Omron 3G3M1-A4110-ECT
850 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Bit Description
0 to 15 Minor revision number
16 to 31 Major revision number
Subindex 04 hex Serial Number gives the product serial number.
Index
(hex)
Sub-
index
(hex)
Object name
Setting
range
Unit
Default set-
ting
Data
attrib-
ute
Size
Ac-
cess
PDO
map
Complete
access
Modes of
operation
10E0 --- Node Address
Reload
--- --- --- --- --- --- --- Not possi-
ble
---
00 Number of en-
tries
--- --- 02 hex --- 1 byte
(U8)
RO --- --- ---
01 Configured Sta-
tion Alias value
0000 to
FFFF hex
--- 0 A 2 bytes
(U16)
W --- --- ---
03 ID-Selector vali-
dation
0000 to
FFFF hex
--- 0 A 2 bytes
(U16)
W --- --- ---
This object sets the node address reload function.
Subindex 01 hex Configured Station Alias value is used when the node address is set and updat-
ed from the master
.
Subindex 03 hex ID-Selector validation is used when the node address is set and updated from
the rotary switch.
Index
(hex)
Sub-
index
(hex)
Object name
Setting
range
Unit
Default set-
ting
Data
attrib-
ute
Size
Ac-
cess
PDO
map
Complete
access
Modes of
operation
10F3 --- Diagnosis Histo-
ry
--- --- --- --- --- --- --- Possible ---
00 Number of en-
tries
--- --- 0D hex --- 1 byte
(U8)
RO --- --- ---
01 Maximum Mes-
sages
--- --- 08 hex --- 1 byte
(U8)
RO --- --- ---
02 Newest Mes-
sage
--- --- 00 hex --- 1 byte
(U8)
RO --- --- ---
03 Newest Ac-
knowledged
Message
00 to FF
hex
--- 00 hex A 1 byte
(U8)
W --- --- ---
04 New Messages
A
vailable
---
--- --- --- 1 bit
(BOOL)
RO TxPDO --- ---
05 Flags 0000 to
003F hex
--- 0000 hex A 2 bytes
(U16)
W --- --- ---
06 to
0D
Diagnosis Mes-
sage 1 to 8
--- --- --- --- 30 bytes
(OS)
RO --- --- ---
This object gives up to 8 Diagnosis Messages. It also enables or disables emergency messages.
Subindex 01 hex Maximum Messages gives the number of Diagnosis Messages.
Subindex 02 hex Newest Message gives the subindex where the latest Diagnosis Message is
saved.
Subindex 03 hex Newest Acknowledged Message is used to execute the message clear.
Value Description
0 The slave will clear all messages.
1 to 5 An abort code is returned.
Appendices
A-13
M1 Series EtherCAT Type User’s Manual (I670)
A-2 CoE Objects
A
A-2-4 Communication Objects

Table of Contents

Related product manuals