9 References
9-3 Battery life
BU100RS
98
9-3 Battery life
Battery has a limited life span.
Periodic checks of the lead battery used in the battery unit are required due to the battery
limited lifespan. For the battery checking method, refer to "4-1 Checking the battery".
Battery replacement is recommended before the battery is expired.
Battery life
(The following is expressed based on the battery's trickle life, the service life of a battery
under the condition where low-frequent (once or twice a month) rechargings and
dischargings are performed.)
Battery type Expected battery life
(Ambient temperature 40°C)
Expected battery life
(Ambient temperature 30°C)
Expected battery life
(Ambient temperature 25°C)
UPS
Long-life battery
1.7 years
3.5 years
5 years
BU100RS
Basically, the ambient temperature has a high influence on the battery life.
The periodic recharges are required even if the battery is stored.
The battery self-discharges even if the UPS is not used (i.e., leaving the battery not
charged), and it deteriorates the battery. In the worst case, the battery may become
unusable.
Example of the storing condition and recharging frequencies
100
80
60
40
20
0
0 3 6 9 12 15
40°C 30°C 25°C
Storage period (Month)
Recharge line
Remaining
capacity (%)
<Description>
When the battery is stored at the storage temperature of 25°C, the battery self-discharges
(and the battery level lowers) to approximately 80% over half a year, and to approximately
50% over a year.
Higher the storage temperature is, faster the battery will self-discharge.
Storage temperature
Auxiliary charging interval
40°C or less
2 months
30°C or less
4 months
25°C or less
6 months