A
Appendix
A-4 CP1L Programming Examples
SYSMAC CP1L/CP1E Introduction Manual 155
■Programming Example
●Ladder Program
MOV(021)
D32306 (CP1E: D1206)
#0115
MOV(021)
D32307 (CP1E: D1207)
#7C00
MOV(021)
D32306 (CP1E: D1206)
#0113
MOV(021)
D32307 (CP1E: D1207)
#8800
TIM
#0010
0
W0.00
Contact A
Operation command (1: Start)
Frequency command
60.00Hz (1770 Hex)
W0.01
Contact B
W0.02
Contact C
W0.15
Contact Z
TIM0
A640.01
A640.00
Modbus-RTU easy master function execution bit
Operation command (1: Start)
Frequency command
55.00Hz (157C Hex)
Operation command (1: Start)
Frequency command
50.00Hz (1388 Hex)
Operation command (0: Stop)
Frequency command 00.00Hz
P_First_Cycle
MOV(021)
D32306 (CP1E: D1206)
#0000
Stop operation when communication
starts. Operation command (0: Stop)
Frequency command 00.00Hz
Start Modbus communication 1 second after executing ladder program.
Continue Modbus communication.
P_On
Modbus-RTU easy master function execution normal flag
MOV(021)
D32306 (CP1E: D1206)
#0000
MOV(021)
D32307 (CP1E: D1207)
#0000
MOV(021)
D32307 (CP1E: D1207)
#0000
MOV(021)
D32306 (CP1E: D1206)
#0117
MOV(021)
D32307 (CP1E: D1207)
#7000