4 - 53
4 Basic Operation
E5@C-T Digital Temperature Controllers User’s Manual (H185)
4-9 Determining PID Constants (Autotuning and Manual Setting)
4
4-9-2 RT (Robust Tuning) (Used for Autotuning)
z RT Features
• Even if hunting occurs for PID constants when autotuning is executed in normal mode, it is less
likely to occur when autotuning is executed in RT Mode.
• When the temperature (PV) falls short of the set point for the PID constants when using
autotuning in normal mode, executing autotuning in RT Mode tends to improve performance.
• When the manipulated variable (MV) is saturated, the amount of overshooting may be somewhat
higher in comparison to PID control based on autotuning in normal mode.
This procedure selects RT mode.
Operating Procedure
1
Press the M Key several times in the Advanced Function
Setting Level to display rt (RT: robust tuning).
Advanced Function Setting
Level
2
Press the U or D Key to select on (RT ON).
The default is off.
Temperature
Temperature
Much hunting occurs.
Set value
Set value
Start of control
Start of control
Time
Time
Hunting is reduced.
Temperature
Temperature
Set value
Set value
Start of control Start of control
Time
Time
RT
off
rt
on
rt

Table of Contents

Other manuals for Omron E5*C Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5*C Series and is the answer not in the manual?

Omron E5*C Series Specifications

General IconGeneral
BrandOmron
ModelE5*C Series
CategoryController
LanguageEnglish

Related product manuals