6 - 11
6 Parameters
E5@C-T Digital Temperature Controllers User’s Manual (H185)
6-3 Operation Level
6
stbm
Remaining Standby Time Monitor Operation must be on standby.
• This parameter monitors the remaining standby time.
* The unit is set in the Standby Time Unit parameter. (The default is H-M (hours and minutes).)
z Related Sections
5-15 Program-related Functions (page 5-53)
z Related Parameters
Standby Time (Adjustment Level): Page 6-34
prgt
Elapsed Program Time Monitor
• This parameter monitors the time that has elapsed from the beginning of the program that
is being executed.
* The unit is set in the Program Time Unit parameter. (The default is H-M (hours and minutes).)
z Related Sections
5-15 Program-related Functions (page 5-53)
Function
Monitor
Monitor range Unit
Standby time in hours and minutes: 0.00 to 99.59
Standby time in days and hours: 0.00 to 99.23
Hours and minutes,
or days and hours*
See
See
Function
Monitor
Monitor range Unit
0.00 to 99.59 Hours and minutes, or
minutes and seconds*
See
See

Table of Contents

Other manuals for Omron E5*C Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5*C Series and is the answer not in the manual?

Omron E5*C Series Specifications

General IconGeneral
BrandOmron
ModelE5*C Series
CategoryController
LanguageEnglish

Related product manuals