5 Advanced Operations
5 - 64
E5@C-T Digital Temperature Controllers User’s Manual (H185)
• If the power is interrupted during standby status, the remaining standby time is held (if the Startup
Operation parameter is set to Continue or Manual and the program was running and with manual
operation before the power was interrupted).
z Related Parameters
Monitoring the Remaining Standby Time
• You can change the SP mode if the reset operation is set to stop control.
• The following figure shows an example of changing between Program SP Mode and Fixed SP Mode
during program operation.
• The procedure for the above operation is given below.
• The program will not start if the Reset Operation parameter is set to stop control and the setting of the
Run/Reset parameter is changed to Run in Fixed SP Mode.
Parameter
name
Display Setting range Default Level
Standby Time stb
0.00 to 99.59 (hours.minutes)
0.00 to 99.23 (days.hours)
0.00 Adjustment Level
Standby Time
Unit
s-u
h-m: Hours.Minutes
d-h: Days.Hours
h-m
Advanced
Function Setting
Level
Parameter
name
Display Setting range Default Level
Remaining
Standby Time
Monitor
stbm
0.00 to 99.59 (hours.minutes)
0.00 to 99.23 (days.hours)
Operation Level
5-15-14 Changing the SP Mode
1
Segment N is changed from Program SP Mode to Fixed SP Mode.
2
The fixed SP is changed.
3
Operation is changed from Fixed SP Mode to Program SP Mode in segment N+1.
Time
PSPFSP
Segment N
SP
PSP
PSP→FSP
FSP→PSP
FSP changed.
Segment N+1