6 Parameters
6 - 16
E5@C Digital Temperature Controllers User’s Manual (H174)
This parameter is used to monitor the manipulated variable for the heating control output during opera-
tion.
This parameter is used to monitor the manipulated variable for the cooling control output during opera-
tion.
o
MV Monitor (Heating) The MV Display parameter must be set to ON.
• During standard control, the manipulated variable is monitored. During heating/cooling
control, the manipulated variables on the control output (heating) is monitored.
• The default is OFF and the manipulated variable is not displayed.
Related Parameters
MV Display (Advanced Function Setting Level): Page 6-70
c-o
MV Monitor (Cooling)
The control system must be set to heating/cooling
control.
The MV Display parameter must be set to ON.
• During heating/cooling control, the manipulated variable on the control output (cooling) is
monitored.
• The default is OFF and the manipulated variable is not displayed.
Related Parameters
Standard or Heating/Cooling (Initial Setting Level): Page 6-46
MV Display (Advanced Function Setting Level): Page 6-70
Function
Monitor
Control Monitor range Unit
Standard −5.0 to 105.0 %
Heating/cooling 0.0 to 105.0 %
See
See
Function
Monitor
Control Monitor range Unit
Heating/cooling 0.0 to 105.0 %
See
See